This paper presents the theory and methodology for the adjustment of the negative sequence current protection function (PDF) ANSI 46 of a synchronous generator with poles and poles, for a multifunctional relay SIEMENS 7UM62 that uses for its logic of decision the curve of time of heating allowed of the machine before the increase of the magnitude of negative sequence Also the consequences and the damages that can be caused by the excess of current of negative sequence circulating by the stator of the generator are explained.
In addition, its functional diagram is illustrated by identifying its input signals: data (settings), analog and binary signals; It also describes in detail its decision process and exit signals. This logical diagram was divided into 3 sub-diagrams to identify the causes that originate their outputs: alarms, startup, firing or blocking, this way of illustrating the process by stages allows greater clarity, since the explanation process is more didactic than the one presented by the manufacturer in the manual.
As an example of an illustration, the calculations of the adjustment criteria of the ANSI 46 PDF applied to a
salient pole generator from Unit 1 of the Salvajina Hydroelectric Plant are presented in detail. This protection function protects the machine by heating load imbalance and asymmetric faults.

Alexander Aristizabal, Gerencia de generación, Empresa de energía del pacifico EPSA, Cali, Colombia

En este artículo se presenta la teoría y la metodología para el ajuste de la función de protección de corriente de
secuencia negativa ANSI 46 de un generador sincrónico de polos salientes y de polos lisos, para un relé multifuncional
SIEMENS 7UM62 que utiliza para su lógic a de decisión la curva de tiempo de calentamiento permitido
de la máquina ante el incremento de la magnitud de secuencia negativa También se explican las consecuencias
y los daños que puede provocar el exceso de corriente de secuencia negativa circulando por el estator
del generador. Además, se ilustra su diagrama funcional identificando sus señales de entradas: datos (ajustes),
señales análogas y binarias; también se describe en detalle su proceso de decisión de acuerdo a sus valores de
sus entradas. Este diagrama lógico se dividió en 3 sub-diagramas para identificar las causas que originan sus
salidas de: alarmas, arranque, disparos o bloqueo, esta forma de ilustrar el proceso por etapas permite mayor
claridad, ya que el proceso de explicación es más didáctico que el presentado por el fabricante en el manual.
Como Ejemplo de ilustración se presentan en detalle los cálculos de los criterios de ajuste de la FDP ANSI 46
aplicados para un generador de polos salientes de la Unidad 1 de la Central Hidroeléctrica de Salvajina. Esta
funcion de protección, protege la máquina por calentamiento de desbalance de carga y fallas asimétricas.

1.
Caicedo D G, Aristizabal A. Methodology for the adjustment of the function of the unbalanced load loss protection - negative ansi 46 sequence of a SIEMENS 7UM62 relay synchronous generator. inycomp [Internet]. 2019 Jan. 30 [cited 2024 Dec. 22];21(1):73-90. Available from: https://revistaingenieria.univalle.edu.co/index.php/ingenieria_y_competitividad/article/view/7668

IEEE. Std C50.13 ™ -2014, IEEE Standard for Cylindrical-Rotor 50 Hz and 60 Hz Synchronous Generators Rated 10 MVA and Above, NY (USA); 2014. Available at: 10.1109 / IEEESTD.2014.6811137

The power engineering education committee. Power system relaying committee. IEEE tutorial on the protection of synchronous generators. Pages 57-61, second edition. NY (USA); 2011. Available at: https://es.scribd.com/document/52342402/Z-Proteccion-de-Generadores-IEEE

IEEE. Std C37.102 ™ -2006, IEEE Guide for AC Generator Protection. NY (USA); 2006. Available at:https://ieeexplore.ieee.org/stamp/stamp.jsp?arnumber=4109950

Multifunctional Protection of Machines 7UM62. SIPROTEC. Manual. V4.8 2013. Available in:

https://www.downloads.siemens.com/download- center/Download.aspx?pos=download&fct=getasset&id1=DLA06_3361

IEEE. Std C50.12 ™ -2005, IEEE Standard for Salient-Pole 50 Hz and 60 Hz Synchronous Generators and Generator / Motors for Hydraulic Turbine Applications Rated 5 MVA and Above. NY (USA); 2005. Available in: 10.1109 / IEEESTD.2006.99082

Lozano Herrera JC, Ortegón Henao JD. Adjustment criteria siemens multifunction relay 7UM622 Amaime generation plant. Valle del Cauca: Universidad del Valle; 2013. Available at: http://bibliotecadigital.univalle.edu.co/bitstream/10893/8057/1/CB-0495174.pdf

Spain Gaviria CE. Teaching material of five functions of protection of the Relay 7UM62 of SIEMENS. Undergraduate thesis in Electrical Engineering. Cali- Valle del Cauca: Universidad del Valle; 2017. Available at: http://bibliotecadigital.univalle.edu.co/bitstream/10893/8057/1/CB-0495174.pdf

Generation Management Energy Company of the Pacific SA. EPSA-CELSIA. "Update of coordination study of protections CH Salvajina U1, Cali (CO); 2017. Available at: http://www.celsia.com/Portals/0/Documentos/PDF/salvajina-avanza/boletin-salvajina-007.pdf5.